District Hearing Board Notices

TIME

NOTICE OF DISTRICT HEARING

Hearing Date

12:00pm

District Hearing Board – Hudson Ranch Power I, LLC (03-25REG)

07/09/2025

Hearing Information

County of Imperial

Air Pollution Control District Hearing Board

Wednesday, July 9, 2025 at 12:00 p.m.

NOTICE IS HEREBY GIVEN that a public hearing will be held on Wednesday, July 9, 2025 at 12:00 pm at the Imperial County Air Pollution Control District (ICAPCD) located at 150 South 9th St., El Centro, CA 92243. The purpose of this hearing is to consider a request by Hudson Ranch Power I, LLC, for their geothermal power plant facility located at 409 W. McDonald Road in Calipatria, CA, for a Regular Variance (03-25REG). The requested Regular Variance is for Permit Conditions 11, 12, 13, and 14 of Permit to Operate (PTO) No. 4233A, which pertain to the nitrogen oxides (NOx) emission limits and source test requirements of three emergency generators at the facility. The Permit Conditions are listed below: 

 

11.      The diesel engine of each black start emergency generator shall not exceed the emission limit of 28.58 pounds per hour of NOx emissions.

 

12.      The diesel engine of the emergency standby generator shall not exceed the emission limit of 11.93 pounds per hour of NOx emissions.

 

13.      The diesel engine of each listed black start emergency generator shall be source tested for compliance with the emission limits of Condition 11 within the first 60 days of installation and every three (3) years thereafter. The frequency of source testing may be extended to not less than every 60 months for each black start emergency generator under the following conditions:

 

a.        Each black start generator operates less than 500 hours per 12 month period (as demonstrated by operational logs) and which emit less than 5 tons of NOx per 12 month period. This period may be extended if a source can prove that the each black start generator has not been operated during the calendar year.

 

b.        Each black start generator uses a portable NOx analyzer to take a NOx emission reading to verify compliance with Condition 11 during each quarter in which a source test is not performed. The portable analyzer shall be calibrated and used per Air District Rule 400.3.G.2.b.

 

14.      The diesel engine of the listed emergency standby generator set shall be source tested for compliance with the emission limits of Condition 12 within the first 60 days of installation and every three (3) years thereafter. The frequency of source testing may be extended to not less than every 60 months for the listed emergency generator under the following conditions:

 

a.        The emergency generator operates less than 500 hours per 12 month period (as demonstrated by operational logs) and which emit less than 5 tons of NOx per 12 month period. This period may be extended if a source can prove that the unit has not been operated during the calendar year.

 

b.        The emergency generator uses a portable NOx analyzer to take a NOx emission reading to verify compliance with Condition 12 during each quarter in which a source test is not performed. The portable analyzer shall be calibrated and used per Air District Rule 400.3.G.2.b.

 

Documentation in support of this request is on file at the ICAPCD office, located at 150 South 9th St., El Centro, CA 92243.

 

All interested persons desiring to present evidence on this term may appear at the hearing, and upon being sworn, may provide testimony. For additional information, contact the ICAPCD at 442-265-1800.

THE HEARING BOARD OF THE

IMPERIAL COUNTY AIR POLLUTION

CONTROL DISTRICT

By: Cassi Justice

Clerk of the Hearing Board

Date: June 17, 2025

District Hearing Board Notices

TIME

NOTICE OF DISTRICT HEARING

Hearing Date

12:00pm

District Hearing Board – Western Mesquite Mines, Inc. (Appeal Hearing 05-24APL)

08/20/2025

Hearing Information

County of Imperial

Air Pollution Control District Hearing Board Hearing

Appeal Hearing 05-24APL

POSTPONEMENT FOR NEW DATE

Wednesday, August 20, 2025 at 12:00 p.m.

NOTICE IS HEREBY GIVEN that the public hearing originally scheduled to be held on Wednesday, May 21, 2025, at 12:00 pm at the Imperial County Air Pollution Control District office located at 150 South 9th Street, El Centro, CA 92243 has been postponed until Wednesday, August 20, 2025, at the same time and same location. The purpose of this hearing is to consider an appeal (05-24APL) by Western Mesquite Mines, Inc. located at 6502 E. Hwy. 78, Brawley CA 92227. The appeal is for denial by the Air Pollution Control Officer regarding the interpretation of Rule 206 and Rule 211 for an application for modification of Permit to Operate No. 1920C-7.

 

Documentation of this request is on file at the Air District office, located at 150 South 9th St., El Centro, CA 92243.

 

All interested persons desiring to present evidence on this term may appear at the hearing, and upon being sworn, may provide testimony. For additional information, contact the Imperial County Air Pollution Control District at (442) 265-1800.

THE HEARING BOARD OF THE

IMPERIAL COUNTY AIR POLLUTION

CONTROL DISTRICT

By: Cassi Justice

Clerk of the Hearing Board

Date: May 20, 2025

District Hearing Board Notices

TIME

NOTICE OF DISTRICT HEARING

Hearing Date

12:00pm

District Hearing Board – Western Mesquite Mines, Inc. (Appeal Hearing 04-24APL)

08/20/2025

Hearing Information

County of Imperial

Air Pollution Control District Hearing Board Hearing

Appeal Hearing 04-24APL

POSTPONEMENT FOR NEW DATE

Wednesday, August 20, 2025 at 12:00 p.m.

NOTICE IS HEREBY GIVEN that the public hearing to be held on Wednesday, May 21, 2025, at 12:00 pm at the Imperial County Air Pollution Control District office located at 150 South 9th Street, El Centro, CA 92243 has been postponed until Wednesday, August 20, 2025, at the same time and location. The purpose of this hearing is to consider an appeal (04-24APL) made by Western Mesquite Mines, Inc. located at 6502 E. US Hwy. 78, Brawley, CA 92227. The appeal is for denial by the Air Pollution Control Officer regarding the removal of all “motor vehicles” from Permit to Operate No. 1920C-7, as per Imperial County Air Pollution Control District Rule 202.E.2.a, detailed below:

 

RULE 202-EXEMPTIONS

E.2 – Vehicles

E.2.a – Motor Vehicles as defined by the Vehicle Code of the State of California but not including any article, machine, equipment, or other contrivance mounted on such vehicle that would otherwise require a permit under the provisions of these rules and regulations.

 

Documentation of this request is on file at the Air District office, located at 150 South 9th St. El Centro, CA 92243.

 

All interested persons desiring to present evidence on this term may appear at the hearing, and upon being sworn, may provide testimony. For additional information, contact the Imperial County Air Pollution Control District at (442) 265-1800.

THE HEARING BOARD OF THE

IMPERIAL COUNTY AIR POLLUTION

CONTROL DISTRICT

By: Cassi Justice

Clerk of the Hearing Board

Date: May 20, 2025